Automatic Sprinklers: Underground
Installation of Fire Service Underground Piping, FDC's and Fire Hydrants
Scope
This standard applies to the installation of underground fire service supply piping,
fire department connections, and fire hydrants.
Requirements:
Fire service underground supply piping shall be installed in accordance with National
Fire Protection Association Standard (NFPA) #24, Standard for the Installation of Private
Fire Service Mains, and in accordance with this standard.
Underground Supply Piping
Fire service piping shall not be installed under buildings. When portions of the piping
must penetrate building foundations or footings, it shall be installed per NFPA Std. #24
and protected by a sleeved penetration that provides a minimum two-inch (2") annular clear
space; Underground fire service piping shall not be encased in concrete.
Fire service piping shall not cross property lines.
When an existing structure is added to, resulting in an additional sprinkler system
riser being provided, it shall be supplied from the existing fire service main and FDC.
(See "Post indicator valves" below for valving arrangements)
Prior to connection to the fire sprinkler system, all underground fire service piping
shall be subjected to a hydrostatic test at 200 psi for a period of 2 hours. After completion
of the test, the piping shall be flushed as outlined in the NFPA standard.
Post Indicator Valves
New sprinkler systems shall be provided with a Post Indicator Valve (PIV) for system
control. (Exception: approved back-flow prevention assemblies utilizing (OS&Y) valves)
One-story buildings having multiple system risers, (i.e., large warehouses or industrial
buildings), shall have a single main supply PIV installed at the street, while the other
risers may have exterior wall mounted PIV's or Outside Screw and Yolk (OS&Y) control valves.
Main system PIV's (or back-flow prevention assemblies controlling sprinkler systems) shall
be installed on the street address side of the building, not more than five (5') feet
behind the back edge of the sidewalk (when a sidewalk is provided running parallel to
the street and is within ten (10') feet of the street/curb line), and in no case shall
the PIV or control valve assembly be more than twenty (20') feet from the street/curb line.
For buildings three (3) or more stories in height, the PIV or control valve assembly
shall be installed at the street for main system control, with individual floor control
valves provided within the building, located in a protected stairway enclosure.
Fire Department Connections
The fire department connection (FDC) shall be installed on the street address side of the
building, within ten (10) feet of the main PIV (unless otherwise approved by the Chief due
to practical difficulties). FDC's shall be equipped with a minimum of two (2), two-and-one-half
(2-1/2") inch national standard threaded inlet couplings. Exception: FDC's supplying private
on-site fire hydrants shall have a minimum four (4) way inlet coupling.
Orientation of the FDC shall be such that hose lines may be readily and conveniently
attached to the inlets without interference.
FDC's shall be painted safety yellow.
Fire Hydrants
Required fire hydrants shall be installed such that the center of the 4 inch hose outlet is
not less than eighteen (18") inches above the final grade.
When required by the Chief, fire hydrants shall be protected by approved bollards, installed
per fire department standards.
Fire hydrants shall be painted safety yellow. Note: Private on-site hydrants supplied
by the sprinkler system FDC shall have the top portion of the hydrant (approximately 4 inches)
painted white.
|